Overheating analysis metrics reference#

This page describes the overheating metrics that epinterface.analysis.overheating calculates from the hourly EnergyPlus SQL output. GloBI calculates these metrics only when the manifest has an overheating_config (see section D of the tutorial).

All series must have 8760 hourly timesteps per year. The functions use arrays with shape (zones, timesteps) and raise an error for other shapes.

Output tables#

The postprocessor overheating_results_postprocess returns an OverheatingAnalysisResults object. GloBI saves four of its tables:

GloBI dataframe key Attribute Function Columns
BasicOverheating basic_oh calculate_basic_overheating_stats Total Hours [hr]
ExceedanceDegreeHours edh calculate_edh EDH [degC-hr]
HeatIndexCategories hi calculate_hi_categories … [hr], one per category
ConsecutiveExceedances consecutive_e_zone calculate_consecutive_hours_above_threshold Streak [hr], Integral [deg-hr]

The results object also has a fifth table, zone_at_risk (from compute_zone_at_risk). GloBI does not save it.

In GloBI outputs, each table also has the feature index of the building (building_id, feature.semantic.*, ...) in front of the index levels below. GloBI saves ConsecutiveExceedances only if at least one streak occurs.

Inputs#

  • \(T_{\mathrm{db},z,t}\): zone dry-bulb air temperature (°C), from Zone Mean Air Temperature.
  • \(\mathrm{RH}_{z,t}\): zone relative humidity (%), from Zone Air Relative Humidity.
  • \(T_{\mathrm{r},z,t}\): mean radiant temperature (°C), from Zone Mean Radiant Temperature. Only EDH uses this input.
  • Thresholds: heat_thresholds and cold_thresholds in the overheating config. The defaults are 26, 30 and 35 °C (heat) and 10 and 5 °C (cold).

The zone weights \(w_z\) are the zone floor areas. The functions normalize the weights so that they sum to 1: \(\tilde{w}_z = w_z / \sum_j w_j\).


1. BasicOverheating (calculate_basic_overheating_stats)#

What it measures: the number of hours with a dry-bulb temperature above a heat threshold (overheating) or below a cold threshold (underheating). This metric does not correct for humidity or radiant temperature.

Per-threshold, per-zone hour counts#

For each heat threshold \(T^{\mathrm{heat}}_k\) and each zone \(z\):

\[H^{\mathrm{over}}_{k,z} = \sum_{t=0}^{8759} \mathbf{1}\bigl[T_{\mathrm{db},z,t} > T^{\mathrm{heat}}_k\bigr].\]

For each cold threshold \(T^{\mathrm{cold}}_\ell\) and each zone \(z\):

\[H^{\mathrm{under}}_{\ell,z} = \sum_{t=0}^{8759} \mathbf{1}\bigl[T_{\mathrm{db},z,t} < T^{\mathrm{cold}}_\ell\bigr].\]

These are the zone-level values: one hour count for each threshold and zone.

Building-level aggregates (same thresholds)#

For each overheat threshold \(T^{\mathrm{heat}}_k\):

Group column Formula or rule
Any Zone \(\sum_t \mathbf{1}\bigl[\exists z: T_{\mathrm{db},z,t} > T^{\mathrm{heat}}_k\bigr]\): the hours in which at least one zone is above the threshold.
Zone Weighted \(\sum_z \tilde{w}_z\, H^{\mathrm{over}}_{k,z}\): the weighted average of the zone hour counts. It is not the number of hours in which the weighted mean dry-bulb temperature is above \(T\).
Worst Zone \(\max_z H^{\mathrm{over}}_{k,z}\): the largest zone hour count for the threshold.
Equally Weighted The row mean over all zone columns plus Any Zone, Zone Weighted and Worst Zone. Thus it is not equal to \(\frac{1}{N}\sum_z H^{\mathrm{over}}_{k,z}\), unless the three aggregate columns are equal to that mean.

The same four groups apply to the underheat thresholds, with \(T_{\mathrm{db},z,t} < T^{\mathrm{cold}}_\ell\) and the zone counts \(H^{\mathrm{under}}_{\ell,z}\).

Output shape and meaning#

  • Index levels: Polarity (Overheat | Underheat), Threshold [degC], Aggregation Unit (Building | Zone), Group.
  • Column: Total Hours [hr].
  • Building rows: the four groups above (Any Zone, Zone Weighted, Worst Zone, Equally Weighted).
  • Zone rows: one row for each zone, with the zone name in Group. The value is the hour count \(H^{\mathrm{over}}_{k,z}\) or \(H^{\mathrm{under}}_{\ell,z}\).

Interpretation: this is the simplest view of overheating and underheating. It counts the hours that are outside the dry-bulb limits, and gives several ways to combine the zones into one building value.


2. ExceedanceDegreeHours (calculate_edh)#

What it measures: exceedance degree-hours (EDH) of the Standard Effective Temperature (SET), not of the dry-bulb temperature. pythermalcomfort.models.set_tmp calculates SET for each hour from \(T_{\mathrm{db}}\), \(T_{\mathrm{r}}\) and \(\mathrm{RH}\). It also uses the ThermalComfortAssumptions of the config: metabolic rate met (default 1.1), clothing clo (default 0.5) and air speed v (default 0.1 m/s).

\(\mathrm{SET}_{z,t}\) is the SET for zone \(z\) at hour \(t\) (°C).

Hot side (overheat)#

For each heat threshold \(T^{\mathrm{heat}}_k\) and zone \(z\):

\[\mathrm{EDH}^{\mathrm{hot}}_{k,z} = \sum_{t=0}^{8759} \max\bigl(0,\, \mathrm{SET}_{z,t} - T^{\mathrm{heat}}_k\bigr).\]

Unit: °C·h (degree-hours). Each hour adds the positive part of \(\mathrm{SET} - T\), and the sum covers the full year.

Cold side (underheat)#

For each cold threshold \(T^{\mathrm{cold}}_\ell\) and zone \(z\):

\[\mathrm{EDH}^{\mathrm{cold}}_{\ell,z} = \sum_{t=0}^{8759} \max\bigl(0,\, T^{\mathrm{cold}}_\ell - \mathrm{SET}_{z,t}\bigr).\]

Building-level aggregates#

For the Overheat thresholds:

  • Zone Weighted: \(\sum_z \tilde{w}_z\, \mathrm{EDH}^{\mathrm{hot}}_{k,z}\).
  • Worst Zone: \(\max_z \mathrm{EDH}^{\mathrm{hot}}_{k,z}\).

For the Underheat thresholds:

  • Zone Weighted: \(\sum_z \tilde{w}_z\, \mathrm{EDH}^{\mathrm{cold}}_{\ell,z}\).
  • Worst Zone: \(\max_z \mathrm{EDH}^{\mathrm{cold}}_{\ell,z}\).

Output shape and meaning#

  • Index levels: Polarity (Overheat | Underheat), Threshold [degC], Aggregation Unit (Building | Zone), Group.
  • Column: EDH [degC-hr].
  • Zone rows: the EDH of each zone for each threshold.
  • Building rows: only Zone Weighted and Worst Zone.

Interpretation: EDH increases with both the magnitude and the duration of discomfort beyond a threshold. It does not only count hours. It uses the same threshold temperatures as the config, but applies them to SET, not to the dry-bulb temperature.


3. HeatIndexCategories (calculate_hi_categories)#

What it measures: the apparent temperature from the Rothfusz regression (heat index in °F), sorted into the NOAA categories. The table counts the hours in each category with several aggregation rules.

Step A — Heat index in °F#

For each zone \(z\) and hour \(t\), the function converts the dry-bulb temperature to Fahrenheit: \(T_{\mathrm{f}} = T_{\mathrm{db}} \cdot \frac{9}{5} + 32\). \(\mathrm{RH}_{z,t}\) is in percent (0–100):

\[ \begin{aligned} \mathrm{HI}_{z,t} &= -42.379 + 2.04901523\, T_{\mathrm{f}} + 10.14333127\, \mathrm{RH} \\ &\quad - 0.22475541\, T_{\mathrm{f}}\, \mathrm{RH} - 6.83783\times 10^{-3}\, T_{\mathrm{f}}^2 - 5.481717\times 10^{-2}\, \mathrm{RH}^2 \\ &\quad + 1.22874\times 10^{-3}\, T_{\mathrm{f}}^2 \mathrm{RH} + 8.5282\times 10^{-4}\, T_{\mathrm{f}}\, \mathrm{RH}^2 - 1.99\times 10^{-6}\, T_{\mathrm{f}}^2 \mathrm{RH}^2 . \end{aligned} \]

Step B — Category index (NOAA, by \(\mathrm{HI}\) in °F)#

Category Rule (heat index °F)
Extreme Danger \(\mathrm{HI} \ge 130\)
Danger \(105 \le \mathrm{HI} < 130\)
Extreme Caution \(90 \le \mathrm{HI} < 105\)
Caution \(80 \le \mathrm{HI} < 90\)
Normal \(\mathrm{HI} < 80\)

Each zone-hour gets one category.

Step C — Building-level “Zone Weighted” series#

The building heat index for each hour is the weighted mean of \(\mathrm{HI}_{z,t}\) over the zones:

\[\overline{\mathrm{HI}}_t = \sum_z \tilde{w}_z\, \mathrm{HI}_{z,t}.\]

The function sorts this series into the same categories. The result is the Zone Weighted row: the hour count for each category.

Step D — Other building-level series#

  • Modal per Timestep: for each hour \(t\), the function takes the modal category over the zones. If two or more modes tie, it takes the mode with the largest category index, which is the most severe (see cat_index_map). Then it counts the hours in each category.
  • Worst per Timestep: for each hour \(t\), the function takes the maximum category index over the zones (the most severe category). Then it counts the hours in each category.

Step E — Zone-level block#

For each zone \(z\), the function counts the hours (of 8760) in each category.

Output shape and meaning#

  • Index levels: Aggregation Unit (Building | Zone), Group.
  • Columns: one for each category: Extreme Danger [hr], Danger [hr], Extreme Caution [hr], Caution [hr], Normal [hr].
  • Building rows: three groups: Modal per Timestep, Worst per Timestep and Zone Weighted. For each of these rows, the categories sum to 8760.
  • Zone rows: one row for each zone, with the zone name in Group.

Interpretation: the heat index is a humidity-adjusted discomfort index, in the NOAA °F form. Zone Weighted gives one combined heat index for each hour. Worst per Timestep and Modal per Timestep show how often the building is in a bad category when you look at all zones in each hour.


4. ConsecutiveExceedances (consecutive_e_zone / calculate_consecutive_hours_above_threshold)#

What it measures: each maximal run of consecutive hours with \(T_{\mathrm{db},z,t} > T^{\mathrm{heat}}_k\), for each heat threshold. For each cold threshold, each maximal run with \(T_{\mathrm{db},z,t} < T^{\mathrm{cold}}_\ell\). This metric uses only the dry-bulb temperature, as BasicOverheating does (EDH uses SET).

Run detection#

The hourly excess for overheating at threshold \(T^{\mathrm{heat}}_k\) is:

\[\Delta^{\mathrm{over}}_{k,z,t} = T_{\mathrm{db},z,t} - T^{\mathrm{heat}}_k.\]

An hour is part of an overheat streak if \(\Delta^{\mathrm{over}}_{k,z,t} > 0\) (strictly above the threshold). Consecutive hours with this property make one run. The run stops when \(\Delta^{\mathrm{over}}_{k,z,t} \le 0\) or when the year ends.

For underheating at \(T^{\mathrm{cold}}_\ell\):

\[\Delta^{\mathrm{under}}_{\ell,z,t} = T^{\mathrm{cold}}_\ell - T_{\mathrm{db},z,t}.\]

An hour is part of an underheat streak if \(\Delta^{\mathrm{under}}_{\ell,z,t} > 0\) (strictly below the threshold). The runs are the maximal sets of consecutive hours with this property.

Per-run quantities#

For each run \(r\) of length \(L_r\) (hours):

  • Streak length \(L_r\): the number of hours in the run (Streak [hr]).
  • Integral of the run: \(\sum_{t \in \mathrm{run}\,r} \Delta_{k,z,t}\), where \(\Delta\) is \(\Delta^{\mathrm{over}}\) or \(\Delta^{\mathrm{under}}\). Unit: °C·h (Integral [deg-hr]). For a constant excess \(\delta\) over the run, the integral is \(L_r \cdot \delta\).

The runs are in time order for each threshold and zone. The function makes one column for each run, then stacks the columns and removes the empty values. Thus the table has one row for each run. To get the longest streak of a zone, aggregate the rows yourself.

Output shape and meaning#

  • Index levels: Polarity (Overheat | Underheat), Threshold [degC], Zone, and Streak Index (the number of the run in the year: 00000, 00001, …).
  • Columns: Streak [hr], Integral [deg-hr].
  • No building-level aggregation: the table has only zone and threshold rows. It does not use the zone weights.

Interpretation: BasicOverheating counts how many hours are outside a limit. This table shows how those hours are grouped: long continuous warm periods or many short ones. The integral also shows how far \(T_{\mathrm{db}}\) is past the threshold during each run.

Downstream use: if a threshold in OverheatingAnalysisConfig has streak_failure or integrated_streak_failure, compute_zone_at_risk uses this table to flag zones. It counts the runs longer than a limit, or sums the integrals of the long runs.


Relationship between the four outputs#

Aspect BasicOverheating ExceedanceDegreeHours HeatIndexCategories ConsecutiveExceedances
Primary variable Dry bulb \(T_{\mathrm{db}}\) SET Rothfusz HI (°F) Dry bulb \(T_{\mathrm{db}}\)
Threshold use Config heat/cold °C Config heat/cold °C on SET Fixed HI °F bands Config heat/cold °C
Unit Hours (counts) °C·h (EDH) Hours per category Hours per run + °C·h per run integral
Building rollups Yes Yes Yes No